The right range for a low-pressure application comes from the normal differential pressure, not the line pressure. Set the span so normal operation sits in a useful part of the scale, leave room for start-up surges, and confirm the result in the model code. The yokogawa EJA110E high-performance differential pressure transmitter uses a single-crystal silicon resonant sensor and delivers a 4-20 mA DC output. It suits air, gas, steam, and liquid service when the span matches the process. Below, I explain how I check each factor before requesting a quote.
A simple worksheet is the first thing I do when I review a range. It's important to write down the average, minimum, and maximum difference pressures, as well as the static pressure, the process temperature, and the level of accuracy the control loop needs. Draft, filter loading, and air ducts are all low-pressure jobs that only need a few inches of water column. One inch of water column is equal to 0.249 kPa air pressure. Most of the time, a range chosen without those numbers is too broad. I ask the tech to write down the real DP at low, normal, and high load when the datasheet only shows line pressure.
A lot of buyers get these two terms mixed up. There is a difference in pressure between the high and low sides. Pressure that is the same on both sides is called static pressure. If the pressure in a duct is close to atmospheric, it might show 2 inH2O of DP. If the pressure is hundreds of psi, it might show the same DP. As an extra variable, the EJA110E measures static pressure with a reference accuracy of ±0.5%. This means that you can keep an eye on both numbers with the same device. Still, look at more than just the DP span. Check the model code for the line pressure number and the overpressure limit as well.
How you read the DP signal changes because of the app. DP changes with the square of the flow in flow service. It takes 50% flow to make only 25% of full-scale DP, and it takes 25% flow to make about 6%. When you size a low-pressure range, it's important to think about the minimum flow. To find DP in level service, multiply density by gravity times height. This means that a water column of one meter height creates 9.81 kPa. To the equation, you need to add the vessel pressure, the wet or dry legs, and the zero elevation. Just before I suggest a range, I run these numbers to see if the low end of the process is in a useful part of the range.
A single-crystal silicon resonant sensor, which is part of Yokogawa's DPharp technology, is used in the Yokogawa EJA110E high-performance differential pressure transmitter. The sensor responds to the difference in pressure, and the electronics turn it into a 4-20 mA DC output that can be sent to a DCS, PLC, or flow computer. The gadget checks the flow, level, density, and pressure of gases, liquids, or vapors. It can also show static pressure or keep an eye on it from afar. Technicians can change parameters from afar without having to go to the field. That saves time in plants where cables run for a long way or where taps are hard to get to.
These numbers from the product description help me with my low-pressure tests:
| Parameter | DP (main variable) | SP (auxiliary variable) |
|---|---|---|
| Reference accuracy | ±0.055% | ±0.5% |
| Response time | 90 ms | 360 ms |
| Long-term stability | ±0.1% URL over 10 years | – |
| Overpressure effect | ±0.03% URL | – |
| Range ratio | 100:1 | – |
Use these as points of reference. The range you choose, the calibration, and the placement all affect how accurate the yokogawa EJA110E high-performance differential pressure transmitter is, so ask for the numbers for your exact range. When stability is given against the upper range limit (URL), it means that a very small range has a bigger share of that error. Remember this when you look at a low span next to a wide span.
Critical loops can be certified by a third party. The performance and reliability of the transmitter were approved by TÜV Rheinland and Exida. The unit also meets the practical safety standards of IEC 61508:2010 and IEC 61511:2004. SIL2 is met by a single unit, and SIL3 is reached by a duplicate arrangement. Because the sensor sends frequency data all the time, even when the process pressure stays the same, a failure is seen right away. During normal operation, Yokogawa's patented Back-Check method does a calculation backward to make sure the quality of the measurements. People who work in low-pressure loops, where signals move slowly, need a constant check to tell the difference between a real process change and an instrument fault.
Instead of selecting the line's greatest potential pressure, choose the range that is located around the line's usual operating point. One of the suitable ranges for a filter is from 0 to 10 inH2O, which places the reading of 3 inH2O and the alert number of 6 inH2O in the center of the range. Due to the fact that the identical signal would only be able to fit into a very tiny portion of the 4-20 mA output spanning the range of 0 to 100 inH2O, it would be difficult for the control system to detect even minute changes. For the purpose of providing a working guideline, I consider typical operation to be between forty and seventy percent of span when the technique permits it. After that, I compare the alert points to the top limit of the range.
If the span is small, it is more likely to overrange, but when the width is large, it is less susceptible to fluctuations in the span. A number of factors, including start-up, shut-down, blocked taps, and errors with the valves, may all contribute to DP levels that are unusually high. While the EJA110E is subject to an overpressure effect of ±0.03% URL, the DPharp sensor is equipped with mechanical safety features inside the diaphragm to safeguard it from the occurrence of overpressure events. Nevertheless, there is no room for error in a span that is almost constantly at its maximum capacity. I first consider the restriction that is most likely to be transitory and the one that covers the broadest range, and then I choose the shortest span that still covers it. Additionally, the 100:1 range ratio enables you to adjust the specified range at a later time, provided that you remain within the parameters of the model.
The ultimate decision needs to be based on the whole Yokogawa model code as well as the most recent instructions. The range of capsules, materials that are moist, process connections, output, and alternatives are all fixed by it, which means that even a little variation may have a significant impact on the results. If you have a very short span, you should evaluate the EJA110E in comparison to other kinds, such as the Rosemount 3051 or the Yokogawa EJA120E. The EJA120E is a product that Yokogawa manufactures for reduced differential pressure spans. Have a look at the most current datasheets with regard to each. The range, the static pressure number, the accuracy, the diagnostics, the links, and the support should all be included in a brief compliance table that you create. Choose the model that is appropriate for the size rather than the brand name.
A DP is created when gas and steam move through an orifice plate, venturi tube, or flow valve. The EJA110E then changes this DP into a 4-20 mA signal. The flow computer needs to know the pressure and temperature of the gas in order to correctly figure out its mass or volume. The transmitter records both static and moving pressure, so it can be used by itself to give the flow computer information about the line state. Because steam adds condensation, the impulse-line slope and condensation management need to be done right. The rules for pressure-differential flow systems are set by ISO 5167, so compare your main part to it. Test the expected flow with the least amount of pressure in low-pressure ducts, as the DP may be very low at that point.
A liquid column creates a pressure that is proportional to its height and density. This is how level measurement works. Join the top of the tank to the bottom, and let air out of the bottom of the tank. Use a wet or dry leg to connect the low side of a closed tank to the vapor space. For the offset, set it to zero elevation or suppression. This is also how density is measured at a fixed height: when the height stays the same, DP changes as density does. Level and density are two of the things that the yokogawa EJA110E high-performance differential pressure transmitter can measure. Keep in mind that density changes with temperature, which means that when the fluid warms up, the level number may move.
DP goes up in small steps over days or weeks because filters and strainers take a long time to fill up. Resolution and a steady zero are the most important things. A clean filter may read close to zero, while a clogged one may only read a few psi. On the product page, it says that filter DP tracking can be used in water cleaning. The transmitter's long-term stability of ±0.1% URL over 10 years makes it possible to look at trends over many maintenance cycles. Set the alarm to the factory-recommended DP port, and then pick a span that puts that point close to 70 to 80 percent of scale. The same method can be used to check the levels of steam and water in power plants.
Most of the problems I see are caused by a few mistakes: sizing the span based on pipeline pressure instead of DP, picking a range that is too wide, and not taking changes in density or temperature into account. Just as many complaints are made about installation mistakes. Impulse lines that don't have the right slope can trap gas or liquid; lines that aren't level can give false DP; and vibrations or bad insulation can make taps freeze or make noise. Wet materials that don't match can rust in chlorides or hydrogen sulfide. 316L stainless steel and Teflon flange seals are listed in the product description. Before you order, make sure that these materials are compatible with the fluid you need to seal. When the model is first turned on, write down the model number, range, units, and dampers.
A well-chosen range is safe when it is calibrated well. Safely separate the transmitter, even out the manifold, and check that the zero is correct. Then, use calibrated pressure points to go across the span, write down the results for "as found" and "as left," and check the service again after the repair. Check the orientation of the mounting, the high and low links, the grounding, and the shielding. For your specific setup, use the approved wiring plan. Before you replace the transmitter, check the process conditions and impulse lines if the readings don't seem right. The self-diagnostic feature is useful in this case because it shows sensor issues separately from changes in the process. For future checks, keep the calibration certificates in the loop file.
Quotation mistakes can be avoided with a full RFQ. Include the model code or replacement reference, the normal and maximum DP, the temperature, the fluid, the connections, the materials that will be wet, the output, the certifications, the accessories, the calibration documents, the quantity, the delivery location, and the date that you need the item. Add a nameplate photo for replacements. Check sellers' model codes, original paperwork, warranties, and customer service after the sale to make sure the products they sell are real. HLX is a licensed Yokogawa distributor, and our technical and after-sales engineers have worked in the field for over ten years. We sell original items and fix or replace broken ones during the warranty period of the Yokogawa EJA110E high-performance differential pressure transmitter.
The process, not the catalog, is what you should use to choose a range for low-pressure service. The span is made up of the normal, minimum, and maximum DP, static pressure, and temperature. Flow and level calculations show if the low end stays measurable. A single-crystal silicon resonant sensor, a 4–20 mA output, a 100:1 range ratio, and ±0.055% reference accuracy are all part of the yokogawa EJA110E high-performance differential pressure transmitter. Those numbers still depend on the span and placement that were chosen. A narrow span makes the signal more sensitive but also increases the risk of going too far out of range, so the span needs to be able to balance these two needs. The selection process is finished with the right model code, materials that work with it, clean impulse lines, and proof of calibration. An in-depth RFQ makes sure that the quote is correct.
Do not use the line pressure for the average, minimum, and maximum DP. Put normal operation in a useful part of the span, leave room for transients, and check the full model code to make sure the capsule range is correct.
Yes. It talks about the flow, amount, density, and pressure of gases, liquids, or vapors in the product description. Flow needs a main part like an orifice plate, and level needs information about density, vessel pressure, and leg configuration.
It's not. That number is the main variable's base accuracy. How well something works depends on its span, calibration, and installation.
Send your process datasheet or nameplate photo to HLX at sales01@hlx8.com, and our engineers will review your range, materials, and delivery needs. As an authorized Yokogawa distributor and a yokogawa EJA110E high-performance differential pressure transmitter supplier, we offer original products, quick delivery, and warranty support from a team with over ten years of experience.
1. ISO 5167-1: Measurement of Fluid Flow by Means of Pressure Differential Devices Inserted in Circular Cross-Section Conduits Running Full, Part 1: General Principles and Requirements, 2022
2. IEC 61508: Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems, 2010
3. IEC 61511: Functional Safety – Safety Instrumented Systems for the Process Industry Sector, 2016
4. ANSI/ISA-12.27.01: Requirements for Process Sealing Between Electrical Systems and Flammable or Combustible Process Fluids, 2011
5. Instrument Engineers' Handbook, Volume 1: Process Measurement and Analysis, 2003
6. Flow Measurement Engineering Handbook, 1996
Our customers’ satisfaction speaks for our quality — contact us to experience the same reliable service.